Today's peak was 905 kW at 13:00, well inside what DTC pays for. One panel on Level 2 is running hot.
Power now
842 kW
896 kVA · power factor 0.94
Energy {{per.label}}
{{per.mwh}} MWh
{{per.vs}}
Cost {{per.label}}
AED {{per.aed}}
Sample tariff · AED 0.44 per kWh
Carbon {{per.label}}
{{per.co2}} t CO₂
Grid factor 0.40 kg per kWh
Solar now
96 kW
11% of the building's use
Demand today against the contract
DTC's contract allows 1,100 kVA (about 1,034 kW at today's power factor). Peak so far is 88% of it.
TodayTypical rest of dayContracted
1,034 kW
0006121823
{{hour.label}}{{hour.text}}
Where energy goes today
{{r.name}} {{r.sub}}{{r.kwh}} kWh · {{r.pct}}
{{splitNote}}
Main incomer
Phase 1
231.2 V
1,284 A
Phase 2
230.6 V
1,312 A
Phase 3
232.0 V
1,276 A
Power factor
0.94
Frequency
50.01 Hz
Voltage distortion
2.1%
Current distortion
6.8%
Phases are balanced within 3%, and power factor is above the 0.90 where penalties start.
Measured by the main meter · EM-MDB-01 · every minute
Sub-boards
1 panel running hot
Board
Feeds
Now
Today
Load
Panel temperature
{{b.name}}
{{b.feeds}}
{{b.kw}} kW
{{b.kwh}} kWh
{{b.temp}}
SMDB-L2 is at 44 °C, above its 40 °C limit, and has been warming since 11:00 at 58% load. A loose connection is the usual cause. Ask for a thermal scan.
Solar on the roof
610kWh today · 96 kW now
061218
Saved AED 268 today. Output is 4% below the clear-sky estimate, so panels may need cleaning soon.
EV charging2 of 8 charging
{{e.id}}{{e.state}}{{e.kw}}
146 kWh today · chargers 3–8 are free in bays B1-101 to B1-106.
Backup power
Generator
Standby
Fuel 86% · about 19 h
Last test run
3 days ago
20 min, passed
UPS load
38%
Server and safety loads
UPS battery
42 min
Healthy
Read only. The generator starts itself if mains power is lost.